        Schindler DDE Configuration/Testing Checklist
                
                
                    
                        
    - Last updated
 
    - 
        
    
 
 
                        - 
    Save as PDF
 
                        -     
        
 
                    
                
            
        
                
                
            
            
                
Server Role
Installed Applications
    - MS SQL
 
    - LocalSync
 
    - ServerManager
 
    - SchindlerInterface
 
BluSKY Verification
In Setup>Facility>Banks
    - Elevator banks are setup as Schindler destination
 
    - Elevator banks have unique numbers corresponding to Schindler documentation
 
    - Elevator banks have cars according to Schindler documentation
 
In Setup>Facility>Cars 
    - Each car has a unique number corresponding to the Schindler documentation. You must configure all cars, even when they are not needed for the function of the system
 
    - First car in the bank has correct floors served by its bank
 
    - Each floor has the correct landing number according to the Schindler documentation
 
In Setup>Destination Keypads
    - Each keypad has an IP address according to Schindler documentation
 
    - Each keypad assigned to a correct floor
 
    - Each keypad has a name that clearly associates it with the bank, floor and unique keypad number
 
In Setup>Interfloor Matrix
    - Each keypad has floor/schedule pair for each floor in its bank
 
    - For the commission, all floors in every keypad have "Always Off" schedule. This makes floors public and will not lock the building when connecting to Schindler
 
Test Cards
    - At least two cards are ready for testing
 
    - At least two persons have assigned above cards and access levels that have assigned floor schedules
 
    - One person has all the floors in the building. Another person has some floors in the building
 
Server
    - Server is created in BluSKY
 
    - Elevator banks are assigned to the server
 
    - Server role is correctly assigned to the server
 
    - Sync status and data upload are enabled
 
    - Data download batch size is set to 500
 
In Setup>DDE Diagnostics
    - System name is visible in DDE diagnostics screen
 
    - Remote server name is visible in DDE diagnostics screen
 
    - Elevator banks and Elevator manufacturer are visible in DDE Diagnostics screen
 
    - Elevator keypads are visible in DDE diagnostics screen
 
    - Bank floor stops are visible in DDE diagnostics screen
 
    - Each Floor stop has a correct landing number in parenthesis according to Schindler unique numbers
 
In Control>Elevators
    - Elevator banks are visible in RTC Elevators screen
 
    - All floors are visible per each bank 
 
    - All floors have correct names
 
    - All floors are "On Schedule"
 
Server Verification
Server
    - The operating system has all the latest updates
 
    - Windows MSMQ and Telnet features are enabled
 
    - Both NIC Cards are clearly named. One to BluB0X network, another to MCE elevator
 
    - Persisting routing to NIC card is applied (See DDE Routing)
 
SQL Server
    - The latest version of SQL Server (from OPS folder) is installed with dual login mode
 
LocalSYNC
    - The latest version of LocalSync is installed with the administrator account
 
    - Correct RemoteServerId is specified in LocalSync.exe.config file
 
    - Start Local Sync in Console and verify that there are no errors
 
    - Verify that LocalSync created BluB0X and BluB0XLogs databases in the SQL server
 
    - Stop LocalSync in the console and start in service mode
 
ServerManager
    - The latest version of the server manager is installed
 
    - Correct RemoteServerId is specified in ServerManager.exe.config file
 
    - Start ServerManager in console mode and verify that there are no errors
 
    - Stop ServerManager in the console and start in service mode
 
SchindlerInterface
    - The latest version of Schindler interface is installed
 
    - Correct RemoteServerId is specified in SchindlerInterface.exe.config file
 
    - Correct SignalRUrl is specified in SchindlerInterface.exe.config file  ( <add key="SignalRUrl" value="https://signalrhub.blub0x.com/signalr"/>)
 
Bench Testing
    - Prepare a test simulator computer. Set the IP address of it corresponding to the subnet of Schindler controller
 
    - Start Schindler Simulator and configure it to the floors/banks/kiosks according to Schindler documentation
 
    - Connect NIC card of the test simulator computer to the Schindler side NIC card of the server
 
    - Start Schindler simulator on the test simulator computer
 
    - Start SchindlerInterface in console mode
 
    - No red line errors in the console screen
 
    - Verify that you can see startup dialog in DDE diagnostics screen
 
    - Verify that all matrixes are coming down from the server to the test simulator and they are visible in DDE diagnostics screen
 
    - Click on heartbeats checkbox in DDE diagnostics screen. Verify that you can see the heartbeats from and to the server
 
    - Uncheck the heartbeats checkbox. Verify that heartbeats stop showing in DDE diagnostics screen
 
    - Change one of the matrices in the BluSKY and verify that the change came down to the test simulator
 
    - Simulate a card swipe on the test simulator and verify that Schindler Interface replies correctly
 
    - Check "Show Person Floors" checkbox. Swipe the card and verify that allowed floor matrix sent to the test simulator is correct
 
    - Disconnect the cable between the test simulator and server. Wait until the Schindler interface reports that Schindler Group(s) is offline
 
    - Verify that this message is visible in the console and also in DDE diagnostics screen
 
    - Reconnect the cable back. Verify that applications reconnected, keypad matrixes were resent, heartbeats started and card swipes are working properly
 
    - Stop the Schindler interface in console mode
 
    - Restart Schindler interface in service mode
 
    - Verify all communication again including matrixes, heartbeats and card swipes
 
    - Verify that card swipes are showing up in the events and event history screens
 
Building Commissioning
    - Remote server is connected and reachable from the internet through TeamViewer
 
    - Local Sync, ServerManager and SchindlerInterface services are running with automatic startup
 
    - Start DDE diagnostics screen in BluSKY and navigate to the system/server/elevator bank
 
    - Stop and restart SchindlerInterface service. Verify that you see the startup communications in DDE diagnostics screen
 
    - Swipe a card at each keypad on every floor and in every elevator bank. Verify that the correct keypad number is reported in the DDE diagnostic screen
 
    - Connect Schindler side NIC Card of the server to the Schindler Layer 3 switch
 
    - Verify that Schindler interface connected to Schindler bank controllers
 
    - Verify that heartbeats are coming and going
 
    - Verify that the keypad matrixes were sent and you can change them
 
    - Verify that the floors open
 
    - Verify that card swipes open the correct floors for that card
 
    - Open Elevators RTC screen. Verify that you can open a floor and place it back to schedule
 
    - Do all other verification required by Schindler and building management
 
    - Change the keypads FloorMatrix to the schedules required by the building
 
    - Verify that floors are open or secure according to the applied schedules
 
DDE Routing